Background

 

A tertiary-level Class A general hospital in a certain city (with a building area of ​​150,000 square meters and 1,200 beds) serves as a regional medical center. In recent years, it has added precision equipment such as digital subtraction angiography (DSA) machines and 3.0T magnetic resonance imaging (MRI) machines, as well as intelligent logistics and information platforms. Although the original power supply was designed with dual circuits, the complex load characteristics caused a series of power quality problems, resulting in abnormal medical equipment, data loss, and electricity fines. In order to ensure medical safety and continuous operation, it is necessary to upgrade the core power distribution system.

 

Power Quality Issues

 

Voltage Sags and Fluctuations

Voltage dips and fluctuations (range -20% to +15%) occur due to nearby subway construction and the startup of radiotherapy equipment and central air conditioning in the hospital, causing alarms on ICU ventilators and data loss on endoscopy workstations.

 

Severe Harmonic Pollution

Non-linear loads such as frequency converters and UPS generate harmonics, primarily of the 5th, 7th, and 11th orders, with a local current distortion rate (THDi) reaching 30%, causing transformer overheating, cable insulation aging, and interference with precision equipment such as electrocardiographs.

 

Three-Phase Imbalance and Reactive Power Shortage

Concentrated single-phase equipment leads to a three-phase imbalance exceeding 20%, with many inductive devices resulting in a power factor of only 0.78-0.82, incurring monthly power adjustment costs and significant system losses.

 

Solution

 

After 72 hours of continuous monitoring, a "system-level centralized governance" strategy was adopted, connecting two sets of core equipment in parallel on the low-voltage side of the 1600kVA main transformer:

 

1. NTPS/MP Unified Power Quality Controller

Injects compensation voltage through a series-coupled transformer, correcting ±20% voltage fluctuations in milliseconds (<3ms);

 

2. APF Active Power Filter

Real-time detection of harmonic currents, generating reverse current via an IGBT inverter to filter out harmonics from the 2nd to 50th orders and compensate for three-phase imbalance, solving the problem at its source.

 

Benefit Analysis

 

1. Direct Economic Benefits

System line loss reduced by 15%, power factor penalty eliminated (annual savings of 20,000 RMB); equipment maintenance frequency reduced by 70%, maintenance costs decreased; transformer capacity effectively increased by 20%, delaying expansion investment.

 

2. Medical and Operational Benefits

Key indicators met targets: THDi decreased from 38.4% to 7.1%, THDu decreased from 5.1% to 2.5%, power factor improved to 0.99, voltage fluctuation controlled within ±3%; no further equipment malfunctions or data loss occurred in ICUs, operating rooms, etc.; image quality of MRI and other equipment improved; lifespan of core medical equipment extended, fundamentally ensuring medical safety.